GE Fanuc 90-30 Ethernet (Gen1)
Review the following information for setting up and configuring the GE Fanuc 90-30 Ethernet (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Ethernet |
Validated devices/series | GE Fanuc 90-30 series |
To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
- Step 3: Configure the List of Registers
If the device is configured for Ethernet access, find its network parameters. Otherwise, use Otherwise, use PLC software on your computer to configure the device for Ethernet access.
Refer to the following device details:
- Device: GE Fanuc 90-30 IC693CPU363
- Device type (driver): GE 90-30 Series (Ethernet)
- I/F: Ethernet
Parameter | Value |
---|---|
Type | GE Fanuc |
Driver | GE Fanuc 90-30 Ethernet (Gen1) |
Network Address | The device address you defined in Step 1 |
Port | 18245 |
Name | Value Type | Address Format | Min Address | Max Address | Description |
---|---|---|---|---|---|
I_Bit | bit | DDDDD | 1 | 32768 |
|
Q_Bit | bit | DDDDD | 1 | 32768 |
|
M_Bit | bit | DDDDD | 1 | 32768 |
|
G_Bit | bit | DDDDD | 1 | 32768 |
|
T_Bit | bit | DDDDD | 1 | 32768 |
|
SA_Bit | bit | DDDDD | 1 | 32768 |
|
SB_Bit | bit | DDDDD | 1 | 32768 |
|
SC_Bit | bit | DDDDD | 1 | 32768 |
|
S_Bit | bit | DDDDD | 1 | 32768 |
|
I | word | DDDDD | 1 | 32753 |
|
Q | word | DDDDD | 1 | 32753 |
|
M | word | DDDDD | 1 | 32753 |
|
G | word | DDDDD | 1 | 32753 |
|
T | word | DDDDD | 1 | 32753 |
|
SA | word | DDDDD | 1 | 32753 |
|
SB | word | DDDDD | 1 | 32753 |
|
SC | word | DDDDD | 1 | 32753 |
|
S | word | DDDDD | 1 | 32753 |
|
R | word | DDDDD | 1 | 32768 |
|
AI | word | DDDDD | 1 | 32768 |
|
AQ | word | DDDDD | 1 | 32768 |
|
W | word | DDDDDDD | 1 | 5000000 |
|