Quickstart Guide
...
Industrial Systems Connection ...
LS Industrial System

LS XBM Serial (Gen1)

6min

Review the following information for setting up and configuring the LS XBM Serial (Gen1) driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Serial

Validated devices/series

LS Electric XBM LS Electric XBC LS Electric XGK

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device



To configure your device:

  1. Note down the following information and refer to it when needed.

    Device: LS XBM-DR165

    Communication I/F: RS232. Refer to the following figure.

    LS XBM Serial reference
    LS XBM Serial reference
    
  2. Launch XG5000 v.3.71 software and click Online > Online Settings.
  3. Set up COM port, and then click Auto Detect.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

LS Industrial System

Driver

LS XBM Serial (Gen1)

Communication Port

Local Serial connection file path

Data Bits

8

Baud Rate

115200

Parity

Even, Odd, None

Stop Bits

1



Name

Value Type

Address Format

Min Address

Max Address

Description

PW_bit

bit

DDDDdd

0

204715

I/O device bit

MW_Bit

bit

DDDDdd

0

204715

Internal device bit

LW_Bit

bit

DDDDDdd

0

1126316

Communication device bit

KW_Bit

bit

DDDDdd

0

255915

Preservation device bit

FW_Bit

bit

DDDDdd

0

204715

Special device bit

DW_Bit

bit

DDDDDdd

0

3276715

Data register bit

UW_Bit

bit

DDDDdd

0

633115

 

RW_Bit

bit

DDDDDdd

0

3276715

 

SX

bit

DDDDD

0

12799

Relay for step control bit

TX

bit

DDDD

0

2047

Timer device bit

CX

bit

DDDD

0

2047

Counter device bit

PW

word

DDDD

0

2047

I/O device

MW

word

DDDD

0

2047

Internal device

LW

word

DDDDD

0

11263

Communication device

KW

word

DDDD

0

2559

Preservation device

FW

word

DDDD

0

2047

Special device

SW

word

DDD

0

127

Relay for step control

DW

word

DDDDD

0

32767

Data register

UW

word

DDDD

0

6331

Analog data register

NW

word

DDDDD

0

21503

Communiction data register

ZW

word

DDD

0

127

Index register

TW

word

DDDD

0

2047

Timer current value

CW

word

DDDD

0

2047

Counter current value

RW

word

DDDDD

0

32767

 

ZRW

word

DDDDD

0

32767

 

TSW

word

DDDD

0

2047

Setup value

CSW

word

DDDD

0

2047

Setup value