The DeviceHub agent acts as a proxy between OPC DA and the Manufacturing Connect Edge system. It allows you to search for available OPC DA Servers and provides a list of tags for the selected server. Multiple servers can be selected.&#x20;

:::hint{type="warning"}
**Note:** DeviceHub Agent is no longer supported.
:::

Review the following use case for connecting and configuring the DeviceHub Agent in Manufacturing Connect Edge.&#x20;

# Important

- To install DeviceHub Agent, your machine must support the following software versions:
  - Windows 10.0.14393
  - Windows SDK version 10.0.18362.0
  - Visual Studio 16 2019
- The DeviceHub Agent must be run on the same host as the OPC DA Server, and DCOM must be configured. For more information, see [Configure DCOM for OPC DA Connections](docId\:Vd2DPnEIa92A8SSbxo85u).
- The DeviceHub Agent supports reading up to 5000 tags from the OPC DA server. It does not support parallel write.
- The DeviceHub Agent does not support OPC Classic Historical Data Access (HDA) or OPC Classic Alarms and Events (AE).
- It is possible to configure multiple connections to several DeviceHub Agent instances inside a Manufacturing Connect Edge or multiple Manufacturing Connect Edge instances using only one DeviceHub Agent application. You can create each connection using the **Add (+)&#x20;**&#x69;con.&#x20;
- The DeviceHub agent includes options to export tags to a CSV file. The CSV file can then be used to import the tags to Manufacturing Connect Edge. The status of the tags are checked periodically. Sending tags to DeviceHub is the preferred method.

# Before You Begin

Download the DeviceHub Agent EXE file from Manufacturing Connect Edge by navigating to **System&#x20;**> **Support&#x20;**&#x69;n the *File Downloads* section.&#x20;

***

Setting up the DeviceHub Agent includes the following tasks:

- Step 1: Add DeviceHub Agent Device to DeviceHub
- Step 2: Create API Token
- Step 3: Install Matrikon OPC Explorer and Simulation and Testing Tool
- Step 4: Set up DeviceHub Agent
- Step 5: Connect the OPC DA Explorer
- Step 6: Send Tags to DeviceHub
- Step 7: View Tag Data

## Step 1: Add DeviceHub Agent Device to DeviceHub

**To add the DeviceHub Agent device to DeviceHub:**

1. In Manufacturing Connect Edge, navigate to **DeviceHub&#x20;**> **Devices**.&#x20;
2. Click **Add New Device**.&#x20;
   The *Connect Device&#x20;*&#x64;ialog box appears.

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/MW7zis1BnilOZb31BvnT0_addnewdevice.png" size="76" width="1078" height="645" caption="Add new device icon" position="center" showCaption="true" indent="2"}

3. In the **Device Type** drop-down list, select **OPCUA**.&#x20;
4. In the **Driver Name** drop-down list, select **DeviceHub Agent**.&#x20;
5. Enter a name for the device. The device name you configure is used for the Device name parameter in the DeviceHub Agent configuration.
6. (Optional) Select the **Enable alias topics&#xA0;**&#x63;heck box. This allows you to name the Topic ID when creating a Tag.
   - If you enable alias topics during device creation or modification, DeviceHub stops publishing to raw topics and publishes only to alias topics.
   - Manufacturing Connect Edge substitutes "." (period) in aliases with "/" (forward slash).
7. Click **Add Device**.&#x20;
   The device appears in the Devices pane.&#x20;

# Step 2: Create API Token

Follow the steps to [Create API Credentials](docId\:wVmH8bpJcJJC4SMSOWQ78). Copy the token and store it for later use.&#x20;

# Step 3: Install Matrikon OPC Explorer and Simulation and Testing Tool

:::hint{type="info"}
**Note**: To install these files, you may have to enable the .NET Framework 3.5. See [Microsoft documentation](https://learn.microsoft.com/en-us/dotnet/framework/install/dotnet-35-windows) on this topic to learn more.&#x20;
:::

In this use case, Matrikon Server is used. You can also use Kepware Server or Prosys Server.

**To download Matrikon OPC Explorer and Simulation and Testing Tool:&#x20;**

1. Visit the [Matrikon ](https://matrikonopc.com/)website.&#x20;
2. From the Matrikon search bar, enter **OPC Simulation Server Download**, and click **Search**.
3. Click the **OPC Simulation Server Download&#xA0;**&#x6C;ink.
4. From the download page, enter your first name, last name, and email address, and then click **Download Now**.
5. From the registration form, enter your account information, and then click **Download Now**.
   An activation email is sent from Matrikon.
6. Click the link provided in the email.
   Use your email address as your user name, and the password you provided in the form as your password for the [http://www.matrikonopc.com/portal](http://www.matrikonopc.com/portal) URL.
7. Click **Download Now**.
   The MatrikonOPCSimulation.exe file downloads to your hard drive.
8. Install the MatrikonOPCSimulation file.
9. From the Matrikon search bar, enter **MatrikonOPC Explorer Download**, and click **Search**.
10. Click the **MatrikonOPC Explorer Download&#xA0;**&#x6C;ink.
11. From the download page, click **Download Now**.
12. Install the MatrikonOPCExplorer filie.

The server configuration is by default. You can add an alias configuration. Explorer is used to connect to the OPC DA server and browse the tags.

# Step 4: Set Up DeviceHub Agent

You can now set up the DeviceHub Agent by connecting to the OPCDA server and DeviceHub in Manufacturing Connect Edge.&#x20;

**To set up the DeviceHub Agent:&#x20;**

1. Open the DeviceHub Agent EXE file you downloaded.
2. From the **Main&#x20;**&#x74;ab, click the **Add&#x20;**&#x62;ox.&#x20;
   The *Add connection* dialog box appears.

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/Co0ElC-ULon1cn-EleGmI_add-connection-devicehub-agent-dialog-box-3000.png" size="80" width="528" height="452" caption="Add connection dialog box" position="center" showCaption="true" indent="2"}

3. Click the **Detect&#x20;**&#x69;con.
   The servers are detected and appear in the OPCDA server drop-down list. The OPCDA host is **localhost&#xA0;**&#x62;ecause the OPC DA server is installed on the same machine as Manufacturing Connect Edge.

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/6M_Gmndrp9LGVFk8zb_vd_detect-icon.png" size="80" width="530" height="484" caption="Detect icon" position="center" showCaption="true" indent="2"}

4. Select an option from the **OPCDA server&#xA0;**&#x64;rop-down list.
5. Configure the *Server&#x20;*&#x73;ettings section.&#x20;
   - **Host**: Enter the IP address for your Manufacturing Connect Edge instance.&#x20;
   - **Port**: The port value should be the same one configured for the DeviceHub Agent device in Manufacturing Connect Edge.&#x20;
   - **Device name**: Enter the device name you configured for the DeviceHub Agent device in Manufacturing Connect Edge.&#x20;
   - **API key**: Paste the API key created in Step 2.&#x20;
6. Click **OK**.
   The OPC DA driver is added in the DeviceHub Agent in another tab, and the tags for the selected server are viewable in the tags box.
7. Click the **Connect&#x20;**&#x69;con.&#x20;
   The DeviceHub Agent connects to DeviceHub in Manufacturing Connect Edge.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/cNwe0soYlJwpdM1si-1Ej_connect-icon.png" size="80" width="753" height="680" position="center" showCaption="false" indent="2"}

8. Return to the Manufacturing Connect Edge instance and navigate to **DeviceHub**.&#x20;
9. Confirm that the DeviceHub Agent tile shows a *Connected&#x20;*&#x73;tatus.&#x20;

If you need to remove a connection in the DeviceHub Agent application, select the tab for the connection you want to remove and go to **Connections&#x20;**> **Remove connection**.&#x20;

# Step 5: Connect the OPC DA Explorer

**To connect the OPC DA Explorer:**

1. Open the MatrikonOPC Explorer.
2. Under the **Localhost&#xA0;**&#x65;ntry in the hierarchy, click the **Matrikon.OPC.Simulation.1&#xA0;**&#x65;ntry.
3. Click the **Connect&#xA0;**&#x62;utton.
   Connection information appears in the *Server Status* panel.

You will need to connect the OPC Explorer to the Simulation and Testing Tool.&#x20;

**To connect the OPC DA Explorer:**

1. Open the MatrikonOPC Explorer.
2. Under the **Localhost&#xA0;**&#x65;ntry in the hierarchy, click the **Matrikon.OPC.Simulation.1&#xA0;**&#x65;ntry.
   If you get the error message "Matrikon OPC explorer machine is not browsed", go to **View&#x20;**> **Options&#x20;**> **General&#x20;**&#x61;nd select the **Registry&#x20;**&#x63;heck box in the *OPC Server Browsing* section.&#x20;
3. Click the **Connect&#xA0;**&#x62;utton.
   Connection information appears in the *Server Status* section.

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/sNDapxH3_XYG8RFVRYCtY_image.png" size="80" width="1093" height="767" caption="Server Status section" position="center" showCaption="true"}

# Step 6: Send Tags to DeviceHub

You can send tags from the DeviceHub Agent applicaiton directly to DeviceHub in Manufacturing Connect Edge. This is the recommended method to add tags to the DeviceHub device.&#x20;

**To send tags to DeviceHub:**

1. Make sure the DeviceHub agent is disconnected from DeviceHub.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/1SKC7qqTGf4gQCBrLbljx_disconnect.png" size="70" width="840" height="833" position="center" showCaption="false" indent="2"}

2. Select the check box for tags you want to send. Alternatively, you can use the **Select all tag**s and **Unselect all tags** icons.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/BvjyRNpPVWa2RbeCKH_4o_select-tags-to-send-to-devicehub.png" size="70" width="840" height="833" position="center" showCaption="false" indent="2"}

3. Click the **Connect&#x20;**&#x69;con to connect to DeviceHub in Manufacturing Connect Edge.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/hMA5WPOwK47d1B6Y5HU9g_connect-icon.png" size="70" width="753" height="680" caption="The Connect icon" position="center" showCaption="true" indent="2"}

4. Click the **CSV&#x20;**&#x69;con and select **Send Tags**.&#x20;
   A message displays that the tags were successfully sent.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/75CC5ufi19bH7deGdOomz_send-tags-icon.png" size="70" width="706" height="800" caption="The Send tags option" position="center" showCaption="true" indent="2"}

You can also add tags to the DeviceHub device in the following ways:

- Use [Browse Tags](docId\:OLXXOdRwNLM-IkP2gPS-4).&#x20;
- Use the Export CSV option in the DeviceHub Agent application. Then, follow [ Step 3: Upload Populated CSV File of Tags](docId\:h5heqIcXrCY3NCH9KBg9I).&#x20;



# Step 7: View Tag Data

You can use the [Flows Manager](docId\:q4JyT-_6f9wEAqu53lw3b) or [Analytics](docId\:dXCE9032oQIlIGIMolvlm) in Manufacturing Connect Edge to view the tag data.&#x20;

**To view tag data in the Flows Manager:**

1. In Manufacturing Connect Edge, navigate to **DeviceHub&#x20;**>**&#x20;Tags**.
2. Select the DeviceHub Agent device.&#x20;
3. Click the **Copy&#x20;**&#x69;con for the tag you want to view.&#x20;
4. Navigate to the **Flows Manager&#x20;**&#x61;nd create a new flow. See [Create a Flow](docId\:VeeOD3N3SLCAsdLEedZBr) to learn more.&#x20;
5. Drag the **DataHub Subscribe** and **Debug&#xA0;**&#x6E;odes to the canvas and wire them together.

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/8FImKkXONq4uHiXRX165S_nodes.png" size="80" width="835" height="410" caption="The DataHub Subscribe and Debug nodes" position="center" showCaption="true" indent="2"}

6. Double-click the **DataHub Subscribe&#xA0;**&#x6E;ode.&#x20;
   - In the **Topic&#x20;**&#x66;ield, paste the tag ID you copied earlier.&#x20;
   - If needed, configure the Datahub Subscribe connection. See the "Step 3: Configure Connector Nodes" section in [Create a Flow](docId\:VeeOD3N3SLCAsdLEedZBr) to learn more.
   - Click **Done**, and then **Deploy**.&#x20;
7. Click the **Debug&#x20;**&#x69;con.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/UKUluHffouXWWGwIByZcC_debug-icon.png" size="80" width="1589" height="532" caption="The Debug icon" position="center" showCaption="true" indent="2"}

8. Drag the message window up and review the messages. A `"success": true` message confirms the connections is successful.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/q_GGrcpUi02K1Ba5tQe9B_debug-messages.png" size="80" width="1589" height="863" position="center" showCaption="false" indent="2"}



**To view tag data in Analytics:**

1. In Manufacturing Connect Edge, navigate to **Analytics**.&#x20;
2. Click **Add processor&#x20;**&#x61;nd select **DataHub Subscribe**.&#x20;
3. In the **Topic&#x20;**&#x66;ield, paste the tag ID you copied earlier.&#x20;
4. Click **Save**.&#x20;
5. Click the **View&#x20;**&#x69;con.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/HnqqzaX_BOogIU69IfYop_view-analytics-datamce.png" size="70" width="473" height="371" caption="The View icon" position="center" showCaption="true" indent="2"}

6. Review the messages. A `"success": true` message confirms the connections is successful.&#x20;

::Image[]{src="https://api.archbee.com/api/optimize/SSUUxKZUk9bFTEPNn_6Zo/tm5u9S8vVsyf0dALSSGDu_review-analytics-datamce.png" size="80" width="1402" height="805" caption="Instance Messages" position="center" showCaption="true" indent="2"}