Quickstart Guide
...
Mitsubishi
Gen 2 Drivers

Mitsubishi QJ71E71

6min

Review the following information for setting up and configuring the Mitsubishi QJ71E71 driver.

Note: We recommend the Mitsubishi Q/L Ethernet driver to connect to QJ71E71 modules, because it has more efficient communication with the PLC and supports more data types.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

MELSEC-Q

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use GX Works2 v1.560J software on your computer to configure the device for Ethernet access.

Note: Only one connection is allowed per port defined in the PLC.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

Mitsubishi

Driver

Mitsubishi QJ71E71

Network Address

The device address you defined in Step 1

Port

5002

Station ID

1



Name

Data Type

Address Format

Min Address

Max Address

Description

B

bit

DDDDD

0

32237

Link Relay

CC

bit

DDDDD

0

25471

Counter Coil

CS

bit

DDDDD

0

25471

Counter Contact

DX

bit

DDDD

0

8191

Direct Input

DY

bit

DDDD

0

8191

Direct Output

F

bit

DDDDD

0

32237

Annunciator

L

bit

DDDDD

0

32237

Latch Relay

M

bit

DDDDD

0

65535

Internal Relay

S

bit

DDDD

0

8191

Step Relay

SB

bit

DDDDD

0

32237

Special Link Relay

SM

bit

DDDD

0

2047

Special Relay

STC

bit

DDDDD

0

25471

Retentive Timer Coil

STS

 

DDDDD

0

25471

Retentive Timer Current Value

TC

bit

DDDDD

0

25471

Timer Coil

TS

bit

DDDDD

0

25471

Timer Contact

V

bit

DDDDD

0

32237

Edge Relay

X

bit

DDDDD

0

65535

Input Relay

Y

bit

DDDDD

0

65535

Output Relay

CN

word

DDDD

0

1023

Counter current

D

word

DDDD

0

9999

Data Register

R

word

DDDD

0

9999

File Register

SD

word

DDDD

0

2047

Special Register

STN

word

DDDDD

0

25471

Retentive Timer Current Value

TN

word

DDDDD

0

25471

Timer Current Value

W

word

DDDD

0

8191

Link Register

Z

word

DD

0

20

Index Register

ZR

word

DDDDDD

0

999999

File Register