Review the following information for setting up and configuring the Mitsubishi Q/L Ethernet driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

Replaces Gen 1 driver(s)

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

Note: Only one connection is allowed per port defined in the PLC. See the steps below to view and edit the open ports on the PLC.

If the device is configured for Ethernet access, find its network parameters. Otherwise, use PLC software on your computer to configure the device for Ethernet access.

  1. Open the PLC project in GXWorks 2.
  2. From the Navigation panel, click Parameter > PLC Parameter. The PLC Parameter Setting window will open.

    Built-in Ethernet Port Setting
    Built-in Ethernet Port Setting
    
  3. Select the Built-in Ethernet Port Setting tab, and note down the IP Address, Subnet Mask Pattern, Default Router IP Address, and Communication Data Code. To allow the driver to write tag values to the PLC, the check box for Enable online change (FTP, MC Protocol) needs to be checked.
  4. Press the Open Setting button to view the open ports using MC Protocol. If necessary, add more ports.
Document image


Note: If you modify any CPU or module parameters, you must power cycle the PLC after downloading the changes.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Note: If you are using this driver to connect to a QJ71E71 Ethernet module, please be sure to verify the Network ID and Station ID with your device settings.

Parameter

Value

Type

Mitsubishi

Driver

Mitsubishi Q/L Ethernet

Network Address

The device address you defined in Step 1

Network Port

5002

Network ID

0

Station ID

255

Encoding

Select Ascii or Binary



Note: The address format in this Gen 2 driver is different from the replaced Gen 1 drivers for the same device.

Name

Value Types

Address Format

Min Address

Max Address

Description

X

bit

HHHH

0

16383

Input Relay

Y

bit

HHHH

0

16383

Output Relay

M

bit

DDDDD

0

61439

Internal Relay

SM

bit

DDDD

0

2047

Special relay

L

bit

DDDDD

0

32767

Latch Relay

F

bit

DDDDD

0

32767

Annunicator

V

bit

DDDDD

0

32767

Edge Relay

B

bit

HHHH

0

61439

Link Relay

TS

bit

DDDDD

0

25471

Timer Contact

TC

bit

DDDDD

0

25471

Timer Coil

SS

bit

DDDDD

0

25471

Retentive Timer Contact

SC

bit

DDDDD

0

25471

Retentive Timer Coil

CS

 bit

DDDDD

0

25471

Counter Contact

CC

bit

DDDDD

0

25471

Counter Coil

SB

bit

HHHH

0

32767

Special Link Relay

S

bit

DDDDD

0

16383

Step Relay

DX

bit

DDDDD

0

16383

Direct Input

DY

bit

HHHH

0

16383

Direct Output

SD

word, dword, int, dint, real, dreal

DDDD

0

2047

Special Register

SD_string

string

DDDD

0

2047

Special Register

SD_bit

bit

DDDDdd

0

204715

Special Register

CN

word, dword, int, dint, real, dreal

DDDDD

0

25471

Counter Current Value

CN_string

string

DDDDD

0

25471

Counter Current Value

D

word, dword, int, dint, real, dreal

DDDDDDD

0

4184063

Data Register

D_string

string

DDDDDDD

0

4184063

Data Register

D_bit

bit

DDDDDDDdd

0

418406315

Data Register

W

word, dword, int, dint, real, dreal

DDDDDDD

0

4184063

Link Register

W_string

string

DDDDDDD

0

4184063

Link Register

W_bit

bit

DDDDDDDdd

0

418406315

Link Register

TN

word, dword, int, dint, string

DDDDD

0

25471

Timer Current Value

SN

word, dword, int, dint, string

DDDDD

0

25471

Retentive Timer Current Value

R

word, dword, int, dint, real, dreal

DDDDD

0

32767

File Register

R_string

string

DDDDD

0

32767

File Register

R_bit

bit

DDDDDdd

0

3276715

File Register

ZR

word, dword, int, dint, real, dreal

DDDDDDD

0

4184063

Serial Num File Register

ZR_string

string

DDDDDDD

0

4184063

Serial Num File Register

ZR_bit

bit

DDDDDDDdd

0

418406315

Serial Num File Register

Z

word, dword, int, dint, real, dreal

DD

0

20

Index Register

Z_string

string

DD

0

20

Index Register

SW

word, dword, int, dint, real, dreal

DDDD

0

2047

Special Link Register

SW_string

string

DDDD

0

2047

Special Link Register

SW_bit

bit

DDDDdd

0

204715

Special Link Register



Note: To define a tag with the Date datatype, set the Value Type as Word and the Count parameter to 7, which will give an array in the format: [year, month, day, hour, minute, second, day of week]. See the example of the array below:

Array[7] = [2024, 5, 13, 14, 25, 51, 1]