Review the following information for setting up and configuring the GE Fanuc RX3i Serial (Gen1) driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Serial

Validated devices/series

GE Fanuc RX3i Series

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device



To configure your device:

  1. Note down the following information and refer to it when needed.

    Device: GE Fanuc RX3i

    Communication I/F: RS232, refer to the following figure.

    GE Fanuc RX3i Serial reference
    GE Fanuc RX3i Serial reference
    
  2. Launch Proficy Machine Edition v8.0 software to configure the device for Ethernet access.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

GE Fanuc

Driver

GE Fanuc RX3i Serial (Gen1)

Communication Port

Local Serial connection file path

Baud Rate

19200

Data Bits

8

Parity

Even, Odd, None

Stop Bits

1

Station ID

1



Name

Value Type

Address Format

Min Address

Max Address

Description

I

bit

DDDDD

1

32768

Input bit

Q

bit

DDDDD

1

32768

Output bit

M

bit

DDDDD

1

32768

 

G

bit

DDDD

1

7680

 

T

bit

DDDD

1

1024

 

SA

bit

DDD

1

128

 

SB

bit

DDD

1

128

 

SC

bit

DDD

1

128

 

S

bit

DDD

1

25471

 

R

word

DDDDD

1

32640

 

AQ

word

DDDDD

1

32640

Analog Output

AI

word

DDDDD

1

32640

Analog Input