Note: This driver is deprecated as of Manufacturing Connect Edge version 3.10.0. We recommend using Koyo Ethernet (Gen1) instead.

Review the following information for setting up and configuring the Koyo Ethernet driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

Koyo DirectLogic Series Automation Direct DirectLogic PLC Series

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use DirectSoft6 V6.1 software to configure the device for Ethernet access.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

Koyo

Driver

Koyo Ethernet

Network Address

The device address you defined during Step 1

Network Port

428784



Name

Value Types

Address Format

Min Address

Max Address

Description

CCM_31

word

HHHH

0

17056

V

CCM_32

word

HHH

0

512

GX, X, SP

CCM_33

word

HHH

0

832

GY,Y,C,S,T,CT

V

word

OOOOO

0

17055

V-memory

GX

bit

OOOO

0

2047

Global I/O

X

bit

OOOO

0

1023

Real Word Inputs

SP

bit

OOOO

0

1023

Special Purpose Relays

GY

bit

OOOO

0

2047

More Global I/O

Y

bit

OOOO

0

1023

Real Word Outputs

C

bit

OOOO

0

1023

Control Relays

S

bit

OOOO

0

1023

Stage Status Bits

T

bit

OOO

0

255

Timer Status Bits

CT

bit

OOO

0

255

Counter Status Bits