Quickstart Guide
...
Industrial Systems Connection ...
Koyo

Koyo Direct Serial (Gen1)

6min

Review the following information for setting up and configuring the Koyo Direct Serial (Gen1) driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Serial

Validated devices/series

Koyo Direct Serial PLC series Automation Direct DirectLogic PLCs

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device



To configure your device:

  1. Note down the following information and refer to it when needed.

    Device: Koyo Direct Logic 06 D0-06DR

    Communication I/F: RS232. Refer to the following figure.

    Koyo Direct Serial reference
    Koyo Direct Serial reference
    
  2. Launch DirectSoft6 v6.1 software and click Reset PLC.
  3. From the Links dialog box, click Add.
  4. Click Next.
  5. Select the PLC family, and then click Next.
  6. Select the protocol, and then click Next.
  7. Click Finish.
  8. Select the link just created for serial communication.

    Serial communication configuration
    Serial communication configuration
    

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

Koyo

Driver

Koyo Direct Serial (Gen1)

Communication Port

Local Serial connection file path

Baud Rate

9600

Data Bits

8

Parity

Even, Odd, None

Stop Bits

1

Station ID

1



Name

Value Type

Address Format

Min Address

Max Address

Description

X

bit

Ddd

1

816

Input Status (Read Only)

Y

bit

Ddd

1

816

Output Status

C

bit

DDDDD

1

2000

Control Bit

T

bit

DDDDD

1

500

Timer Status

CT

bit

DDDD

1

250

Counter Status

SC

bit

DDD

1

1000

System Control Bit

DS

word

DDDD

1

4500

Data Registers

DD

word

DDDD

1

1000

Data Registers (Double Word)

DH

word

DDD

1

500

Data Registers

DF

word

DDD

1

500

Data Registers (Double Word)

XD

word

D

0

8

Input Status Registers

YD

word

D

0

8

Output Status Registers

TD

word

DDD

1

500

Timer Current Values

CTD

word

DDD

1

250

Counter Current Values

SD

word

DDDD

1

1000

System Data Registers

TXT

word

DDDD

1

1000

Text Data Registers