Quickstart Guide
...
Siemens
Gen 2 Drivers

Siemens ISO-on-TCP

5min

Review the following information for setting up and configuring the Siemens ISO-on-TCP driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, use TIA Portal V16 software on your computer to configure the device for Ethernet access.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

Siemens

Driver

Siemens ISO-on-TCP

Network Address

The device address you defined in Step 1

Port

102

Local TSAP

TCP-2

Remote TSAP

Keep this field empty



Name

Data Type

Address Format in Manufacturing Connect Edge

Min Address

Max Address

Description

Basic

byte, word, dword

DDDD

0

8191

Raw Data, Address is an Offset

Buffer

word

D

0

0

Buffer