Quickstart Guide
...
Siemens
Gen 1 Drivers

Siemens Logo Ethernet (Gen1)

6min

Review the following information for setting up and configuring the Siemens Logo Ethernet (Gen1) driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, follow the steps below.

To configure your device:

  1. Note down the following information and refer to it when needed. Device: LOGO BM 24CE Communication I/F: Ethernet. Refer to the following figure.

    Reference image of device
    Reference image of device
    
  2. Set up the IP address under ADMIN mode. The default password to switch from Operator mode is LOGO.
  3. Select Network > IP address.

    Reference image of device
    Reference image of device
    
  4. Enter the IP address for your device. For example: 192.168.447.110.
  5. Log in to the web server to configure the device. The default password is LOGO.
  6. Launch the Logo Soft Comfort v1.08.02 software and select Tools > Transfer > Logo > PC.
  7. Enter the IP address in the Target IP Address field, and then click OK.
  8. Select Tools > Ethernet connection.
  9. From the Configure Ethernet Connection dialog box, click Ethernet Connectors.
  10. From the Local Properties (Server) section, select Accept all connection results.
  11. From the Remote Properties (Client) section, enter the local TSAP in the TSAP field. The local TSAP default is 20.00. For this configuration, the Remote TSAP is set to 21.00.
  12. Click OK.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

Siemens

Driver

Siemens Logo Ethernet (Gen1)

Network Address

The device address you defined during Step 1

Port

102

Local TSAP

4096

Remote TSAP

512



Name

Value Type

Address Format

Min Address

Max Address

Description

I

bit

DD

1

64

Input bit

Q

bit

DD

1

64

Output bit

M

bit

DDD

1

112

 

NI

bit

DDD

1

128

 

NQ

bit

DDD

1

128

 

V

bit

DDDDo

0

14697

 

AI

word

DD

1

16

Analog Input

AQ

word

DD

1

16

Analog Output

AM

word

DD

1

64

 

NAI

word

DD

1

64

 

NAQ

word

DD

1

32

 

VB

byte

DDDD

0

1469

 

VW

word

DDDD

0

1468

 

VD

dword

DDDD

0

1466

 

RTC

wprd

D

1

7