Review the following information for setting up and configuring the Panasonic FP Ethernet (Gen1) driver.

Manufacturing Connect Edge Compatible Series

Compatibility parameter

Compatible items

Driver type

Ethernet

Validated devices/series

FP2

To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:

  • Step 1: Set up and Configure the PLC Device
  • Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
  • Step 3: Configure the List of Registers

Step 1: Set up and Configure the PLC Device

If the device is configured for Ethernet access, find its network parameters. Otherwise, follow the steps below.

To configure your device:

  1. Note down the following information and refer to it as needed.

    Device: Panasonic FP Ethernet FP2SH-60K

    Communication I/F: Ethernet. Refer to the following figure.

    Reference image of device
    Reference image of device
    
  2. Launch Control FPWIN Pro7 v7.2.3.0 software, and then click Online > Communication parameters.
  3. Set up communication parameters, and then click Connect.

Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub



Parameter

Value

Type

Panasonic

Driver

Panasonic FP Ethernet (Gen1)

Network Address

The device address you defined during Step 1

Port

8500



Name

Value Type

Address Format

Min Address

Max Address

Description

X

bit

DDDDdd

0

999915

Input bit

Y

bit

DDDDdd

0

999915

Output bit

R

bit

DDDDdd

0

999915

Internal Relay

L

bit

DDDDdd

0

9999

Link Relay

L_Bit

bit

DDDDdd

0

999915

 

T

bit

DDDD

0

9999

Timer

C

bit

DDDD

0

9999

Counter

SV

word

DDDD

0

9999

Timer/Counter Set Value

EV

word

DDDDD

0

65535

Timer/Counter Elapse Value

DT

word

DDDDD

0

262143

Data Register

LD

word

DDDD

0

8447

Link Register

WX

word

DDDD

0

9999

Input

WY

word

DDDD

0

9999

Output

WR

word

DDDD

0

9999

Internal Relay

WL

word

DDDD

0

9999

Link Relay

FL

word

DDDDD

0

99999

File Register