Siemens S7-200 Serial (Gen1)
Review the following information for setting up and configuring the Siemens S7-200 Serial (Gen1) driver.
Compatibility parameter | Compatible items |
---|---|
Driver type | Serial |
Validated devices/series | S7-200 |
To set up and configure this device in Manufacturing Connect Edge, you will need to do the following:
- Step 1: Set up and Configure the PLC Device
- Step 2: Set up the PLC Device in Manufacturing Connect Edge DeviceHub
- Step 3: Configure the List of Registers
To configure your device:
Note down the following information and refer to it when needed. Device: Siemens CPU 222 Communication I/F: RS485. Refer to the following figure.
- Launch Step7-Micro/WIN software and click Set PG/PC Interface.
- Select PC/PPI Cable, and then click Property.
- From the Local Communication dialog box, select USB.
- Click Communication, and then click Double-Click to Refresh. The device is detected.
Parameter | Value |
---|---|
Type | Siemens |
Driver | Siemens S7-200 Serial (Gen1) |
Communication Port | Local Serial connection file path |
Baud Rate | 38400 |
Data Bits | 8 |
Parity | Even, Odd, None |
Stop Bits | 1 |
Station ID | 1 |
Name | Value Type | Address Format | Min Address | Max Address |
---|---|---|---|---|
I | bit, byte, sint, word, int, dword, dint, real | DDo | 0 | 317 |
Q | bit, byte, sint, word, int, dword, dint, real | DDo | 0 | 317 |
M_Bit | bit | DDo | 0 | 317 |
V_Bit | bit | DDDDo | 0 | 20477 |
S_Bit | bit | DDo | 0 | 287 |
SM_Bit | bit | DDDo | 0 | 5497 |
T_Bit | bit | DDD | 0 | 255 |
C_Bit | bit | DDD | 0 | 255 |
AI | byte, sint, word, int, dword, dint, real | DD | 0 | 31 |
AQ | byte, sint, word, int, dword, dint, real | DD | 0 | 31 |
M | byte, sint, word, int, dword, dint, real | DD | 0 | 31 |
S | byte, sint, word, int, dword, dint, real | DD | 0 | 31 |
SM | byte, sint, word, int, dword, dint, real | DDD | 0 | 549 |
T | dword | DDD | 0 | 255 |
C | word | DDD | 0 | 255 |
V | byte, sint, word, int, dword, dint, real, string | DDDD | 0 | 2047 |